AX-OC-WMW / Occupancy Detector - Wall Mount POA Qty
 <<  |  <  | OVERVIEW | SPECIFICATION | DATASHEETS        

The AX-OC-WMW range of occupancy sensors are designed for use in energy savings systems where the lighting loads are automatically controlled based on occupancy. There is an adjustable timer that switches off the load when the area is no longer occupied. The built-in daylight sensor aids additional energy savings in lighting control applications. The device will turn on the load only if the ambient light is below a preset level.The unit is mounted on a single gang plate for easy installation.
Product Features
• 10.525GHz microwave sensor
• Excellent EMI immunity
• 20 metres detection range
• Built-in light sensor
• 230Vac and 24V versions available
• Touch switch to override the sensor (optional)

Power supply
230 Vac ± 10 % 230V versions
24 Vac/dc ± 10 % for 24V versions

Power consumption
1W maximum
Sensor type
Microwave, 10.525 GHz
Antenna 3dB beam width
Horizontal
Detection range
Up to 20m
Output
Supply voltage for switched live versions. SPST for volt free versions
Terminals
Rising clamp for 0.5-2.5mm2 cable
Contact rating
6A @ 240Vac resistive
Timer adjustability
10 secs to 12 mins
Daylight sensor lux threshold
0-1000lux.(Can be disabled with jumper)
Ambient temperature range
0°C to +50°C
Front plate material
Flame retardant ABS
Dimensions
85 x 85 x 35 mm
Backbox depth
Minimum 26mm
Conformity
EMC
Weight
160gms
Country of origin
UK

AX-OC-WMW.pdf / Occupancy Detector - Wall Mount